Article 430

Motors, Motor Circuits, and Controllers

430

Motors, Motor Circuits, and Controllers

Equipment for General UseNEC 2008NEC 2020NEC 2026

Summary

Motor FLC tables, conductor sizing, overload vs short-circuit protection, and disconnects.

One of the densest exam articles — tables 430.247–250 and Part sections.

  • Motor branch-circuit conductors often 125% of FLC.
  • Overload protection ≠ branch short-circuit protection.
  • Controller and disconnect location rules are tested.

Study notes from the app's code library — always confirm with the official NEC book your AHJ adopts.

Sections in Code Lookup (124)

Practice questions (5)

  1. 1.The maximum rating or setting of a motor branch-circuit short-circuit and ground-fault protective device using an inverse-time breaker is generally _____ of full-load current per Table 430.52, unless the next-size-up exception is used.

  2. 2.Motor branch-circuit conductors supplying a single motor shall have an ampacity of not less than 125% of the motor full-load current per 430.22.

  3. 3.A dual-element (time-delay) fuse used as motor short-circuit and ground-fault protection is generally sized at 175% of FLA in Table 430.52.

  4. 4.A single 10 hp, 230 V, 3-phase motor has a Table 430.250 FLA of 28 A. Minimum conductor ampacity at 125% is:

  5. 5.For that same 28 A motor, the maximum inverse-time breaker from Table 430.52 at 250% is 70 A, and 240.6 standard sizes / 430.52 next-size-up may apply if 70 A will not start the motor.