Conductors for General Wiring
Summary
Conductor types, ampacity tables, temperature correction, adjustment factors, and marking.
Table 310.16 (formerly 310.15(B)(16) in older books) is the everyday ampacity table.
- Ampacity depends on size, insulation, ambient, and bundling.
- Termination temperature limits (110.14) can control conductor size.
- Table number renumbered across years — know your book.
Study notes from the app's code library — always confirm with the official NEC book your AHJ adopts.
Sections in Code Lookup (64)
- 310.1Scope
- 310.2Conductors
- 310.3Stranded Conductors
- 310.4Conductors in Parallel
- Table 310.4(A)Conductor Applications and Insulations Rated 600 Volts
- Table 310.4(B)Thickness of Insulation for Nonshielded Types RHH and RHW Solid Dielectric Insulated Conductors Rated 2000 Volts
- 310.5Minimum Size of Conductors
- Table 310.5Minimum Size of Conductors
- 310.6Shielding
- 310.7Direct-Burial Conductors
- 310.8Locations
- 310.9Corrosive Conditions
- 310.10Temperature Limitation of Conductors
- 310.11Marking
- 310.12Conductor Identification
- Table 310.12Single-Phase Dwelling Services and Feeders
- 310.13Conductor Constructions and Applications
- Table 310.13(A)Conductor Applications and Insulations Rated 600 Volts
- Table 310.13(B)Thickness of Insulation for Nonshielded Types RHH and RHW Solid Dielectric Insulated Conductors Rated 2000 Volts
- Table 310.13(C)Conductor Application and Insulation Rated 2001 Volts and Higher
- Table 310.13(D)Thickness of Insulation and Jacket for Nonshielded Solid Dielectric Insulated Conductors Rated 2400 Volts
- Table 310.13(E)Thickness of Insulation for Shielded Solid Dielectric Insulated Conductors Rated 2001 to 35,000 Volts
- 310.14Aluminum Conductor Material
- 310.15Ampacities for Conductors Rated 0-2000 Volts
- Table 310.15(B)(1)Ambient Temperature Correction Factors Based on 30°C (86°F)
- Table 310.15(B)(2)Ambient Temperature Correction Factors Based on 40°C (104°F)
- Table 310.15(B)(2)(a)Adjustment Factors for More Than Three Current-Carrying Conductors in a Raceway or Cable
- Table 310.15(B)(2)(c)Ambient Temperature Adjustment for Conduits Exposed to Sunlight On or Above Rooftops
- Table 310.15(B)(6)Conductor Types and Sizes for 120/240-Volt, 3-Wire, Single-Phase Dwelling Services and Feeders
- Table 310.15(C)(1)Adjustment Factors for More Than Three Current-Carrying Conductors
- 310.16Ampacities of Insulated Conductors (0–2000V) — reference
- Table 310.16Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts, 60°C Through 90°C, Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)
- Table 310.17Allowable Ampacities of Single-Insulated Conductors Rated 0 Through 2000 Volts in Free Air, Based on Ambient Air Temperature of 30°C (86°F)
- 310.17Ampacities of Single-Insulated Conductors in Free Air
- Table 310.18Allowable Ampacities of Insulated Conductors Rated 0 Through 2000 Volts, 150°C Through 250°C (302°F Through 482°F). Not More Than Three Current-Carrying Conductors in Raceway or Cable, Based on Ambient Air Temperature of 40°C (104°F)
- 310.18Ampacities of Insulated Conductors in Raceway or Cable
- Table 310.19Allowable Ampacities of Single-Insulated Conductors, Rated 0 Through 2000 Volts, 150°C Through 250°C (302°F Through 482°F), in Free Air, Based on Ambient Air Temperature of 40°C (104°F)
- 310.19Ampacities of Single-Insulated Conductors in Free Air
- Table 310.20Ampacities of Not More Than Three Single Insulated Conductors, Rated 0 Through 2000 Volts, Supported on a Messenger, Based on Ambient Air Temperature of 40°C (104°F)
- 310.20Ampacities of Conductors Supported on a Messenger
- Table 310.21Ampacities of Bare or Covered Conductors in Free Air, Based on 40°C (104°F) Ambient, 80°C (176°F) Total Conductor Temperature, 610 mm/sec (2 ft/sec) Wind Velocity
- 310.21Ampacities of Bare or Covered Conductors in Free Air
- 310.60Conductors Rated 2001 to 35,000 Volts
- Table 310.67Ampacities of Insulated Single Copper Conductor Cables Triplexed in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)
- Table 310.68Ampacities of Insulated Single Aluminum Conductor Cables Triplexed in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)
- Table 310.69Ampacities of Insulated Single Copper Conductor Isolated in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)
- Table 310.70Ampacities of Insulated Single Aluminum Conductor Isolated in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)
- Table 310.71Ampacities of an Insulated Three-Conductor Copper Cable Isolated in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)
- Table 310.72Ampacities of an Insulated Three-Conductor Aluminum Cable Isolated in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)
- Table 310.73Ampacities of an Insulated Triplexed or Three Single-Conductor Copper Cables in Isolated Conduit in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)
- Table 310.74Ampacities of an Insulated Triplexed or Three Single-Conductor Aluminum Cables in Isolated Conduit in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)
- Table 310.75Ampacities of an Insulated Three-Conductor Copper Cable in Isolated Conduit in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)
- Table 310.76Ampacities of an Insulated Three-Conductor Aluminum Cable in Isolated Conduit in Air Based on Conductor Temperatures of 90°C (194°F) and 105°C (221°F) and Ambient Air Temperature of 40°C (104°F)
- Table 310.77Ampacities of Three Single-Insulated Copper Conductors in Underground Electrical Ducts (Three Conductors per Electrical Duct) Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C (194°F) and 105°C (221°F)
- Table 310.78Ampacities of Three Single-Insulated Aluminum Conductors in Underground Electrical Ducts (Three Conductors per Electrical Duct) Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C (194°F) and 105°C (221°F)
- Table 310.79Ampacities of Three Insulated Copper Conductors Cabled Within an Overall Covering (Three-Conductor Cable) in Underground Electrical Ducts (One Cable per Electrical Duct) Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C (194°F) and 105°C (221°C)
- Table 310.80Ampacities of Three Insulated Aluminum Conductors Cabled Within an Overall Covering (Three-Conductor Cable) in Underground Electrical Ducts (One Cable per Electrical Duct) Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C (194°F) and 105°C (221°C)
- Table 310.81Ampacities of Single Insulated Copper Conductors Directly Buried in Earth Based on Ambient Earth Temperature of 20°C (68°F), Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C (194°F) and 105°C (221°C)
- Table 310.82Ampacities of Single Insulated Aluminum Conductors Directly Buried in Earth Based on Ambient Earth Temperature of 20°C (68°F), Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C (194°F) and 105°C (221°F)
- Table 310.83Ampacities of Three Insulated Copper Conductors Cabled Within an Overall Covering (Three-Conductor Cable), Directly Buried in Earth Based on Ambient Earth Temperature of 20°C (68°F), Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C (194°F) and 105°C (221°F)
- Table 310.84Ampacities of Three Insulated Aluminum Conductors Cabled Within an Overall Covering (Three-Conductor Cable), Directly Buried in Earth Based on Ambient Earth Temperature of 20°C (68°F), Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°C (194°F) and 105°C (221°F)
- Table 310.85Ampacities of Three Triplexed Single Insulated Copper Conductors Directly Buried in Earth Based on Ambient Earth Temperature of 20°C (68°F), Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures 90°C (194°F) and 105°C (221°F)
- Table 310.86Ampacities of Three Triplexed Single Insulated Aluminum Conductors Directly Buried in Earth Based on Ambient Earth Temperature of 20°C (68°F), Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures 90°C (194°F) and 105°C (221°F)
- Figure 310.60Cable Installation Dimensions for Use with Table 310.77 Through Table 310.86
Practice questions (14)
1.Article 310 covers general requirements for conductors and their type designations, insulations, markings, mechanical strengths, ampacity ratings, and uses.
2.The ampacity tables most commonly used for 60°C / 75°C / 90°C insulated conductors in a raceway, cable, or earth (not more than three current-carrying conductors) are in:
3.From Table 310.16, the 75°C ampacity of 8 AWG copper THHN/THWN is:
4.Ampacity adjustment is generally required when more than three current-carrying conductors are bundled or in a raceway.
5.For 4 to 6 current-carrying conductors in a raceway, the adjustment factor in Table 310.15(C)(1) is:
Pictures

310.16 · Rated 75°C '-#=ʘ

310.6 · Rated 380A at 90°C

210.19 · 210.19(A)(1)(a) example — 44A continuous load

210.19 · 90°C equipment terminals — 210.19(A)(1) Exception No. 2

210.19 · 210.19(A)(1) Ex 2 example — 44A at 90°C terminals

210.19 · Sizing with ampacity adjustment/correction — 210.19(A)(1)(b)

210.19 · Four current-carrying conductors — ampacity after factors

210.19 · Larger of 210.19(A)(1)(a) and (b)

310.1 · Four Current-Carrying Conductors

310.15 · When different size conductors are installed in a raceway,

310.1 · Schedule 40 PVC

310.1 · Part II. Construction Specifications